DC SUSTAINABILITY
DISTRIBUTION CENTERS
WATER - LEVEL 3
Water Fixtures
- Perform an indoor water reduction calculation using the LEED v4 Indoor Water Use Reduction Calculator with the proposed or existing plumbing fixture flow/flush rates to confirm that at least a 30% water use reduction is being achieved
- The following flow/flush rates are recommended:
- 0.35 gpm (1.33 lpm) lavatories
- 1.5 gpm (5.67 lpm) showers
- 1.1 gpf (4.16 lpm) toilets/water closets
- 0.128 gpf (0.48 lpm) urinals
- Ensure that all applicable fixtures* are WaterSense labeled
Note: that water fixture selection criteria should be carefully reviewed against local water regulations.
* All faucets and fixtures except public lavatory and service faucets
** Or local equivalent to WaterSense
Water Metering
- Use existing tenant-level water meters where possible
- Connect with your local sustainability champion to report monthly water use data to for tracking towards targets